RT Max Reset

RT Max Reset

Max Reset

Contact Type: SPDT
Contact material: Silver cadmium oxide
Loads: AC-1 ohmic 10A 400V
AC-3 (motor) 4A 400v
AC-15 (inductive) 3A 400V
Ambient Temperature -50 to 70°c

 

Type of Charge– with designation letters:
A: Vapour charge – sensor must not be the warmest part.
B: Adsorption charge
C: Partial charge – the sensor must not be the coldest part

OrderCode Type Type of Charge Set.Range°C  Fixed Diff at lowest range °C Fixed Diff at Highest range °C Max Sensor Temperature°C  Capillary Tube Length (m)
017-5004 RT101 B 25 > 90 2.4  4.1 300 2
017-5023 RT101 20 > 90  2.4 4.1  300 5
017-5136 RT107 70 > 150 6 1.8 215 2
017-5141 RT107 70 > 150  1.8  215  5
017-5211^  RT120 120 > 215  1.8  260 
017-5214*  RT120  120 > 215  1.8  260 
017-5224 RT123 C 150 > 250 6.5 1.8 260 2
017-5231 RT124 C 200 > 300 5 2.5 350 2
017-5004″ RT115 B 10 > 35 1.8 1.8 92 1
017-5023+ RT115 B 10 > 35 1.8 1.8 92 1
               

 

^ Thermostats fitted with Neon lamp connected to terminal 4
* Thermostats with Tamper-proof seal.
” Can be connected to 220v & 380v
+ Can be connected to 220v

 

RT Data Sheet